• Complies with IEC 61557
• Designed to IP 54 Rating
• Live circuit and wiring connection check LED’s
• Triple ranges insulation tests at 250, 500 and 1000V
• Triple range loop and PSC tests 15mA test current at 200Ω/2000Ω range(No RCD Trip)
• Phase angle selection on RCD ranges
• Polarity switch for continuity tests
• Auto-null facility for continuity tests
• Earth probe for loop impedance testing on extraneous metalwork
• Contact Voltage Reading
• Test of a large kind of RCD’s: Standard, Selective, AC and A (DC sensitive breakers)
Continuity Testing | |
---|---|
Measuring Ranges | 20/200/2000Ω (Autoranging) |
Open Circuit Voltage | >6V |
Short Circuit Current | >200mA DC |
Accuracy | ±(1.5%rdg+3dgt) |
Insulation Testing | |
Measuring Ranges | 20/200MΩ (Autoranging) |
Test Voltage | 250V 500V 1000V DC |
Output Voltage on Open Circuit | 250V+40%-0% 500V+30%-0% 1000V+20%-0% |
Rated Current | > 1mA |
Accuracy | ±(1.5%rdg+3dgt) |
Loop Impedance Testing | |
Rated Voltage | 230V AC +10%-15% [50Hz] |
Voltage Measuring Range | 100 – 250V AC [50Hz] |
Impedance Ranges | 20/200/2000Ω |
Nominal Test Current | 25A (20Ω range) 15mA (200Ω range) 15mA (2000Ω range) |
Accuracy | 20Ω range ±(3%rdg +4dgt) 200Ω range ±(3%rdg +8dgt) 2000Ω range ±(3%rdg +4dgt) |
PSC Testing | |
Rated Voltage | 230V AC +10%-15% [50Hz] |
PSC Ranges | 200A (15mA Test Current) 2000A (25A Test Current) 20kA (25A Test Current) |
Accuracy | PSC accuracy derived from measured loop impedance specification and measured voltage specification |
RCD Testing | |
Rated Voltage | 230V AC +10%-15% [50Hz] |
Trip Current Settings | RCD × 1/2 : 10,30,100,300,500,1000mA RCD × 1 : 10,30,100,300,500,1000mA RCD × 5 : 10,30,100,300mA (on × 5 ranges max current 1A) |
Trip Current Duration | RCD × 1/2 × 1: 2000ms RCD fast: 50ms |
Accuracy | Trip current +10%-0% of test current at 230V Trip time ±(1%rdg + 3dgt) |
Safety Standard | IEC 61010-1 CAT III 300V Pollution Degree 2 IEC 61557 |
---|---|
Power source | LR6 (1.5V) × 8 |
Dimensions | 130(L) × 183(W) × 100(D)mm |
Weight | 1100g approx. |
Included Accessories | *KAPM10 (Molded plug test leads for loop and RCD testing at sockets) 7122B (Test leads) 7132A (External earth probe) Pouch for Test Leads 9121 (Shoulder Strap) Battery LR6 (1.5V) × 8 Instruction Manual |
Optional Accessories | 7133B (Distribution board test leads) |
*KAMP10(EU):European SHUKO plug
KAMP10(UK):British plug(13A)
KAMP10 (AU):Australian plug
KAMP10(SA):South African plug