Specifications
(50/60Hz)
Mounting type | Top-mounting |
---|---|
Cooling capacity(W) | 1150/1300 |
Setting Temperature Range(℃) | 25~45 |
Use Area Temperature(℃) | 20~50 |
Use Area Humidity(%RH) | 10~85 (No condensation) |
External dimensions(mm) | H448×W710×D370 |
Weight(kg) | 44 |
Coating Color | Munsell 5Y 7/1 Equivalent color of light beige |
Rated Voltage(V) | Single-phase AC200 |
Consumption Current: Rated(A) | 3.3/3.4 |
Consumption Current: MAX(A) | 4.0/4.4 |
Starting Current(A) | 12.7/11.6 |
Consumption wattage: Rated(W) | 590/680 |
Consumption wattage: MAX(W) | 740/870 |
Noise Resistance | LEVEL4 by Fast Transient / Burst Immunity Test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust prevention / dust proof protection class | Equivalent to IP54 (internal circulation route) |
Refrigerant / Fill ration(g) | R407C 385g |
Noise (dB (A)) | Approx. about 65/68 |
External Output | Alarm output (No-voltage/normal open: resistive load 250V 2A) |
Display | Internal temperature/Error display LED/RUN LED |
Note)
Cooling capacity : Rated capacity value when external temperature is 35°C, internal setting temperature is 35°C. (measurement conditions:JIS-C-9612 air enthalpy method))
Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.
Rating Value : 35°C ambient temperature, ambient humidity RH 40%.
MAX value: use area temperature at the maximum use area temperature allowed, use area humidity of 40%RH.
Allowable ambient temperature: When used continuously at a low ambient temperature (15 to 20 °C or less), be sure to turn off the power supply as there is a possibility the compressor may operate at a high load.
Non-draining function operating range: At an ambient temperature/panel internal temperature of 35 °C or less and an ambient humidity/panel internal humidity of 85% or less.
Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
Reading an instruction manual well certainly before use and please use it right.
Accessories list
Mounting bolt for main unit | 4 (M6×L12) |
---|---|
Drain hose | 3 |
L-shaped angles | 2 |
Insulation lock ties | 6 |
Washer | 2 |
Air direcrion louver | 1 |
Mounting nut | 2 (M4), 4 (M6) |
Instruction manual | 1 |
Replacement parts list
Condenser side Fan | Circulating fan for G1320EXE |
---|---|
Evaporator side Fan | Outside air fan for G1320EXE |
Filter | ENC-F-44 |
Evaporization filter | Vaporization filter for G1320EXE |
Control PCB | Substrate for G1320EXE |
Note: Check with our sales representative as the delivery lead time varies depending on the inventory status.
*Note that the model, specifications and other details described are subject to change without notice.
External dimensions
(1) Power line : Cord length 3m
(2) Alarm Output Line : Cord length 3m
Diagram of Panel Cutout
*Figure seen from control board outside.
*Please keep screw pace on the occasion of processing.
*Standard panel cut will not be changed even if a model change is carried out (some exceptions apply), but the minimum panel cut dimensions are subject to change without notice.