Specifications
(50/60Hz)
Mounting type | Side-mounting |
---|---|
Cooling capacity(W) | 530 |
Setting Temperature Range(℃) | 25~45 |
Use Area Temperature(℃) | 20~55 |
Use Area Humidity(%RH) | 10~85 (No condensation) |
External dimensions(mm) | H450×W350×D260 |
Weight(kg) | Approx. 19 |
Coating Color | Equivalent color of light beige 5Y 7/1 |
Rated Voltage(V) | Single-phase AC200~240 |
Consumption Current: Rated(A) | 2.3 |
Consumption wattage: Rated(W) | 360 |
Recommended breaker capacity (A) | 5 |
Vibration Resistance | JIS Z0200 Level1 |
Dust prevention / dust proof protection class | Single-phase AC200~240 |
Refrigerant / Fill ration(g) | R1234yf 210g |
Noise (dB (A)) | Approx. 69 |
External Output | Rated voltage normally open : 250 VAC 2A resistive load |
Display | Internal temperature/Error/RUN |
Cooling Capacity : Rated capacity value when external temperature is 35°C and humidity is 40%RH , internal temperature is 35°C and humidity is 40%RH, power source & voltage : 200V.
(Test method: JIS B 8615-1 Indoor air enthalpy test method)
Use area temperature / humidity : Use area temperature / humi dity is not meant to satisfy all conditions in temperature and humidity.
Dust prevention / dust proof protection class : Excluding dra in pipe section
Reading an instruction manual well certainly before use and p lease use it right.