Precision air conditioners – PAU-GR300SE

Thương hiệu : Apiste

Cam kết và Chính sách của TECHNO

  • icon

    Cam kết 100% Hàng chính hãng

  • icon

    Chất lượng cao, đáp ứng đa dạng nhu cầu

  • icon

    Tư vấn kỹ thuật toàn diện và chuyên sâu

  • icon

    Chính sách bảo hành và hỗ trợ nhanh chóng

Specifications

Cooling scheme Air-cooling type
Control models Temperature control
Cooling capacity(W) *1 315 (430)
Thermal capacity(W) *2 250
Dehumidifying capacity(g/㎏(DA)) *3 6.65
Temperature stability(℃) *4 ±0.1
Setting Temperature Range(℃) *5 20 to 30
Use Area Temperature(℃) 20 to 35 (Temperature change gradient: Within 1℃/1h)
Use Area Humidity(%RH) 15 to 85 (Humidity change gradient: within 5%RH/1h) (No condensation)
Air outlet volume(m3/min) 1.2 (Normal mode / Energy saving mode)
0.8 (Dry mode)
External Dimensions(mm) H500×W350×D400 *6
Weight(kg) 32
Coating Color Munsell N-87 Equivalent color of gray
Blower duct connection diameter(mm) φ75
Rated voltage(V) Single-phase AC100 to AC120
Consumption Current(A) *8 3.2(Rated) 4.4(MAX)
Consumption wattage(W) *8 275(Rated) 380(MAX)
Drain connection diameter φ9.53
Refrigerant(g) R1234yf 150g
Exhaust air volume(m3/min) *9 3.7

*1 Cooling capacity is based on a 25℃/50% RH use area temperature and humidity at a distance of 2 meters in front of the duct of a PAU-GR300SE and 4 meters in front of the duct of a PAU-GR800SE.
( ) internal cooling capacity is based on 30℃/70% RH use area temperature and relative humidity at a distance of 2 meters in front of the duct of a PAU-GR300SE and 4 meters in front of the duct of a PAU-GR800SE.
*2 Thermal capacity is based on 25℃/70% RH use area temperature and relative humidity when a distance of 2 meters in front of the duct of a PAU-GR300SE and 4 meters in front of the duct of a PAU-GR800SE.
*3 Dehumidifying capacity is based on 30℃/70% RH use area temperature and relative humidity when operating in dry mode at a distance of 2 meters in front of the duct of a PAU-GR300SE and 4 meters in front of the duct of a PAU-GR800SE.
*4 The temperature and humidity control accuracy is based on the method prescribed in JTMK01 Constant Temperature Humidistat Bath – Performance Testing Method and Performance Display Method (Japan Testing Machine Association). Only the value indicated by the temperature controller built into the air conditioner at the main unit blow off port is guaranteed to be accurate and thermal interference due to the duct etc. is not covered by the precision guarantee. In addition, the purpose of this product is to suppress temperature fluctuations in the air and so the absolute value of the temperature is not guaranteed. (A bias function for compensation is built into the system.)
*5 The temperature and humidity may not be controllable even if they are within the set range depending on the ambient temperature.
*6 Dimensions exclude protruding sections of the control panel, outlet flanges, and castors and their mounts.
*7 Dimensions excluding operation panel protrusions, blowout flanges, and casters.
*8 The consumption current and power consumption indicated these fluctuate depending on the temperature and humidity of the ambient environment and the operating conditions.
*9 Waste heat is discharged from the device because it is air-cooled. (with optional exhaust chamber)

・For the actual installation, check the specifications and precautions stated in the instruction manual.
・Maintain power supply voltage within ±10% of rated voltage.

External dimensions

PAU-GR300SE External dimensions

Temperature / humidity sensor

PAU-GR300SE Temperature / humidity sensor