Specifications

(50/60Hz)

Mounting type Side-mounting
Cooling capacity(W) 800/1000
Setting Temperature Range(℃) 25~45
Use Area Temperature(℃) 20~55
Use Area Humidity(%RH) 10~80 (No condensation)
External dimensions(mm) H730×W300×D230
Weight(kg) 22
Coating Color Munsell 5Y 7/1 Equivalent color of light beige
Rated Voltage(V) Single-phase AC200
Consumption Current: Rated(A) 2.2/1.8
Consumption Current: MAX(A) 2.6/2.9
Starting Current(A) 7.5/7.1
Consumption wattage: Rated(W) 340/350
Consumption wattage: MAX(W) 450/560
Cooling water / Temperature range (℃) 10~40
Cooling water / Flow rate (ℓ/min) 5
Cooling water / Pressure (Mpa) 0.2~0.5
Noise Resistance LEVEL4 by Fast Transient / Burst Immunity Test
Vibration Resistance 5Hz frequency 20mm total amplitude
Refrigerant / Fill ration(g) R134a 100g
Noise (dB (A)) Approx. 57/60
External Output Alarm output (No-voltage/normal open: resistive load 250V 2A)
Display Internal temperature/Error display LED/RUN LED

Note)
Cooling capacity : Rated capacity value when internal temperature is 35°C, Cooling water inlet temperature 35 ℃, supply water amount 7.2 / 7.9ℓ / min. (measurement conditions: JIS-C-9612 air enthalpy method))
Rating Value : 35°C use area temperature, use area humidity RH 40%.
MAX value: use area temperature at the maximum use area temperature allowed, use area humidity of 40%RH.
Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
Reading an instruction manual well certainly before use and please use it right.

Accessories list

Drain hose 3m
Hose band 1
Instruction manual 1

Replacement parts list

Condenser side Fan Circulating fan for NW1120L
Control PCB Substrate for NW1120

Note: Check with our sales representative as the delivery lead time varies depending on the inventory status.
*Note that the model, specifications and other details described are subject to change without notice.

External dimensions

ENC-NW1120L External dimensions

Diagram of Panel Cutout

ENC-NW1120L Diagram of Panel Cutout

[Standard panel cut]
*Figure seen from control board outside.
*Please keep screw pace on the occasion of processing.