Specifications
(50/60Hz)
Mounting type | Side-mounting |
---|---|
Cooling capacity(W) | 2000/2200 |
Setting Temperature Range(℃) | 25~45 |
Use Area Temperature(℃) | 20~55 |
Use Area Humidity(%RH) | 10~85 (No condensation) |
External dimensions(mm) | H1200×W450×D260 |
Weight(kg) | 62 |
Coating Color | Munsell 5Y 7/1 Equivalent color of light beige |
Rated Voltage(V) | Three-phase AC380~415/AC400~460 |
Consumption Current: Rated(A) | 1.7/1.9 |
Consumption Current: MAX(A) | 2.2/2.5 |
Starting Current(A) | 12/13 |
Consumption wattage: Rated(W) | 1000/1200 |
Consumption wattage: MAX(W) | 1350/1700 |
Noise Resistance | LEVEL4 by Fast Transient / Burst Immunity Test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust prevention / dust proof protection class | Equivalent to IP54 (internal circulation route) |
Refrigerant / Fill ration(g) | R134a 300g |
Noise (dB (A)) | Approx. 65/67 |
External Output | Alarm output (No-voltage/normal open: resistive load 250V 2A) |
Display | Internal temperature/Error display LED/RUN LED |
Note)
Cooling capacity : Rated capacity value when external temperature is 35°C, internal temperature is 35°C – 40%. (measurement conditions: JIS-C-9612 air enthalpy method))
MAX value: Value at the maximum ambient temperature allowed and an operating ambient humidity of 40%RH.
Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
Reading an instruction manual well certainly before use and please use it right.
Accessories list
Mounting bolt for main unit | 6 (M8×L25) |
---|---|
Drain hose | 2m |
Insulation lock ties | 1 |
Mounting nut | 2(M8) |
Instruction manual | 1 |
Replacement parts list
Condenser side Fan | Circulating fan for ENC-G2240L |
---|---|
Evaporator side Fan | Outside air fan for ENC-G2240L |
Filter | ENC-F-43 (2 pieces) |
Control PCB | Substrate for ENC-G2240L |
Note: Check with our sales representative as the delivery lead time varies depending on the inventory status.
*Note that the model, specifications and other details described are subject to change without notice.
External dimensions
Diagram of Panel Cutout
ENC-G2240L[Standard panel cut (Left)]*Figure seen from control board outside.
*Please keep screw pace on the occasion of processing.
*Standard panel cut will not be changed even if a model change is carried out (some exceptions apply), but the minimum panel cut dimensions are subject to change without notice.