Specifications
(50/60Hz)
Mounting type | Top-mounting |
---|---|
Cooling capacity(W) | 700/800 |
Setting Temperature Range(℃) | 25~45 |
Use Area Temperature(℃) | 20~50 |
Use Area Humidity(%RH) | 10~85 (No condensation) |
External dimensions(mm) | H338×W670×D353 |
Weight(kg) | 30 |
Coating Color | Munsell 5Y 7/1 Equivalent color of light beige |
Rated Voltage(V) | Single-phase AC200 |
Consumption Current: Rated(A) | 2.6/2.3 |
Consumption Current: MAX(A) | 3.2/3.0 |
Starting Current(A) | 7.5/7.1 |
Consumption wattage: Rated(W) | 435/455 |
Consumption wattage: MAX(W) | 580/600 |
Noise Resistance | LEVEL4 by Fast Transient / Burst Immunity Test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust prevention / dust proof protection class | Equivalent to IP54 (internal circulation route) |
Refrigerant / Fill ration(g) | R134a 250g |
Noise (dB (A)) | Approx. 60/65 |
External Output | Alarm output (No-voltage/normal open: resistive load 250V 2A) |
Display | Internal temperature/Error display LED/RUN LED |
Note)
Cooling capacity : Rated capacity value when external temperature is 35°C, internal setting temperature is 35°C. (measurement conditions:JIS-C-9612 air enthalpy method))
Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.
Rating Value : 35°C ambient temperature, ambient humidity RH 40%.
MAX value: use area temperature at the maximum use area temperature allowed, use area humidity of 40%RH.
Allowable ambient temperature: When used continuously at a low ambient temperature (15 to 20 °C or less), be sure to turn off the power supply as there is a possibility the compressor may operate at a high load.
Non-draining function operating range: At an ambient temperature/panel internal temperature of 35 °C or less and an ambient humidity/panel internal humidity of 85% or less.
Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
Reading an instruction manual well certainly before use and please use it right.
Accessories list
Mounting bolt for main unit | 4 (M6xL12) |
---|---|
Nut with a flange | (M6) 4 / (M4) 2 |
Drain hose | 1 (3m) |
L-shaped angles | 2 |
Insulation lock ties | 6 |
Washer | 2 (M6) |
Air direcrion louver | 1 |
Instruction manual | 1 |
Replacement parts list
Condenser side Fan | Circulating fan for G820EXE |
---|---|
Evaporator side Fan | Outside air fan for G820EXE |
Filter | ENC-F-21 |
Evaporization filter | Vaporization filter fo G820EXE |
Control PCB | Substrate for G820EXE |
Note: Please contact sales representative by availability. Because delivery time varies.
The contents described in other model specifications, since specifications are subject to change without notice, Please note.
External dimensions
Diagram of Panel Cutout
*Figure seen from control board outside.
*Please keep screw pace on the occasion of processing.
*Standard panel cut will not be changed even if a model change is carried out (some exceptions apply), but the minimum panel cut dimensions are subject to change without notice.