• New technology permits safe testing, without the need of direct contact between probes and live wires.
• The insulated crocodile clips can clip insulated cables from φ2.4 to 30mm.
• Phase rotation is indicated by the rotary illumination of LEDs and logical audible tones.
• The instrument can be fixed to a metal panel via the magnet on the back side.
• Wide measuring range for 3 phase installations from 70V to 1000V AC.
• Super brightness function permits clear LED’s indication also in sunshine.
• Complies with IEC 61010-1 CAT IV 600V and CAT III 1000V.
Functions | Phase rotation (Clockwise or Counter Clockwise), Presence of open phase |
---|---|
Detection method | Electrostatic induction |
Measuring voltage range | From 70 to 1000V AC phase to phase (sine wave, continuous input) |
Clamp diameter range | From Ø2.4 to 30mm insulated cables |
Measuring frequency range | 45 to 66Hz |
Phase rotation | Clockwise: Green arrow LEDs “rotate” in clockwise, Green symbol “CW” lits, Intermittent buzzer Counter Clockwise: |
Visual indication | Via LEDs with Super brightness function |
Battery voltage warning | Power LED blinks if battery voltage is too low. |
Test leads | Double insulated cables, length approx. 70cm |
Colours code | L1(U): RedL2(V): WhiteL3(W): Blue |
Applicable standards | IEC 61010-1 CAT IV 600V, CAT III 1000V Pollution degree2, IEC 61326-1, IEC 61557-1, -7 |
Operating temperature & humidity range | Temperature/Humidity Ranges -10 to 50ºC, 80% (no condensation) |
Storage temperature & humidity range | Temperature/Humidity Ranges -20 to 60ºC, 80% (no condensation) |
Power supply (DC battery) | LR6(AA)(1.5V) ×4 * Continuous use: Approx. 100 hours (Auto power off in about 10 min.) |
Dimensions | 112(L) × 61(W) × 36(D) mm |
Weight | 380g approx. |
Included Accessories | 9096 (Carrying case), LR6(AA) × 4, Instruction manual |