Control panel cooling unit – ENC-A5500L

Thương hiệu : Apiste

Cam kết và Chính sách của TECHNO

  • icon

    Cam kết 100% Hàng chính hãng

  • icon

    Chất lượng cao, đáp ứng đa dạng nhu cầu

  • icon

    Tư vấn kỹ thuật toàn diện và chuyên sâu

  • icon

    Chính sách bảo hành và hỗ trợ nhanh chóng

Specifications

(50/60Hz)

Mounting type Side-mounting
Cooling capacity(W) 5000/5500
Setting Temperature Range(℃) 25~45
Use Area Temperature(℃) 25~55
Use Area Humidity(%RH) 10~80 (No condensation)
External dimensions(mm) H1500×W600×D380
Weight(kg) 90
Coating Color Munsell 5Y 7/1 Equivalent color of light beige
Rated Voltage(V) Three-phase AC200
Consumption Current: Rated(A) 5.6/6.0
Consumption Current: MAX(A) 7.1/8.2
Starting Current(A) 29.0/26.2
Consumption wattage: Rated(W) 1650/1850
Consumption wattage: MAX(W) 2150/2650
Noise Resistance LEVEL4 by Fast Transient / Burst Immunity Test
Vibration Resistance 5Hz frequency 20mm total amplitude
Dust prevention / dust proof protection class Equivalent to IP54 (internal circulation route)
Refrigerant / Fill ration(g) R407C 1000g
Noise (dB (A)) Approx. 68.5/68
External Output Cooling operation output/Alarm output (No-voltage/normal open: resistive load 250V 2A)
Display Internal temperature/Error display LED/RUN LED

Note)
Cooling capacity : Rated capacity value when external temperature is 35°C, internal setting temperature is 35°C. (measurement conditions: JIS-C-9612 air enthalpy method))
Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.
Rating Value : use area temperature 35°C , use area humidity RH 40%.
MAX value: Value at the maximum ambient temperature allowed and an operating ambient humidity of 40%RH.
Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
Reading an instruction manual well certainly before use and please use it right.

Accessories list

Mounting bolt for main unit 6 (M10×L25)
Drain hose 2m
Insulation lock ties 1
Mounting nut 2 (M10)
Instruction manual 1

Replacement parts list

Condenser side Fan Circulating fan for A5500L
Evaporator side Fan Outside air fan for A5500L
Filter ENC-F-37 (2 pieces)
Control PCB Substrate for A5500L

Note: Check with our sales representative as the delivery lead time varies depending on the inventory status.
*Note that the model, specifications and other details described are subject to change without notice.

External dimensions

ENC-A5500L External dimensions

(1) Power line : Cord length 3m
(2) Alarm Output Line : Cord length 3m
(3) Cooling operation output Line : Cord length 3m
* The thermistor is inside the suction port of the main body.

Diagram of Panel Cutout

ENC-A5500L Diagram of Panel Cutout