Control panel cooling unit – ENC-G1651L

Thương hiệu : Apiste

Cam kết và Chính sách của TECHNO

  • icon

    Cam kết 100% Hàng chính hãng

  • icon

    Chất lượng cao, đáp ứng đa dạng nhu cầu

  • icon

    Tư vấn kỹ thuật toàn diện và chuyên sâu

  • icon

    Chính sách bảo hành và hỗ trợ nhanh chóng

Specifications

(50/60Hz)

Mounting type Side-mounting
Cooling capacity(W) 1450/1650
Setting Temperature Range(℃) 25~45
Use Area Temperature(℃) 20~55
Use Area Humidity(%RH) 10~85 (No condensation)
External dimensions(mm) H1000×W400×D230
Weight(kg) 38
Coating Color Munsell 5Y 7/1 Equivalent color of light beige
Rated Voltage(V) Single-phase AC100
Consumption Current: Rated(A) 7.6/7.4
Consumption Current: MAX(A) 9.0/9.9
Starting Current(A) 22.3/20.5
Consumption wattage: Rated(W) 580/650
Consumption wattage: MAX(W) 740/870
Noise Resistance LEVEL4 by Fast Transient / Burst Immunity Test
Vibration Resistance Equivalent to JIS Z 0200 Level1
Dust prevention / dust proof protection class Equivalent to IP54 (internal circulation route)
Refrigerant / Fill ration(g) R407C 400g
Noise (dB (A)) Approx. 68/72
External Output Alarm output (No-voltage/normal open: resistive load 250V 2A)
Display Internal temperature/Error display LED/RUN LED

Note)
Cooling capacity : Rated capacity value when external temperature is 35°C, internal setting temperature is 35°C. (measurement conditions:JIS-C-9612 air enthalpy method))
Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.
Rating Value : 35°C ambient temperature, ambient humidity RH 40%.
MAX value: use area temperature at the maximum use area temperature allowed, use area humidity of 40%RH.
Allowable ambient temperature: When used continuously at a low ambient temperature (15 to 20 °C or less), be sure to turn off the power supply as there is a possibility the compressor may operate at a high load.
Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
Reading an instruction manual well certainly before use and please use it right.

Accessories list

Mounting bolt for main unit 6 (M8×L25)
Drain hose 2m
Insulation lock ties 1
Washer 2(M6)
Spacer 6
Air direcrion louver 1
Mounting bolt for louver 2
Mounting nut 2 (M8)
Compound screw 2 (M8)
Instruction manual 1

Replacement parts list

Condenser side Fan Circulating fan for G1651L
Evaporator side Fan Outside air fan for G1651L
Filter ENC-F-45 (2 pieces)
Control PCB Substrate for G1651L/G1652L

Note: Check with our sales representative as the delivery lead time varies depending on the inventory status.
*Note that the model, specifications and other details described are subject to change without notice.

External dimensions

ENC-G1651L External dimensions

(1) Power line : Cord length 3m
(2) Alarm Output Line : Cord length 3m
* The thermistor is inside the suction port of the main body.

Diagram of Panel Cutout

ENC-G1651L Diagram of Panel Cutout

*Figure seen from control board outside.
*Please keep screw pace on the occasion of processing.
*Standard panel cut will not be changed even if a model change is carried out (some exceptions apply), but the minimum panel cut dimensions are subject to change without notice.
The power wire lead-out area is the shaded area or the φ50 machining.