Control panel cooling unit – ENC-G1310LE
Cam kết và Chính sách của TECHNO
-
Cam kết 100% Hàng chính hãng
-
Chất lượng cao, đáp ứng đa dạng nhu cầu
-
Tư vấn kỹ thuật toàn diện và chuyên sâu
-
Chính sách bảo hành và hỗ trợ nhanh chóng
Specifications
(50/60Hz)
| Mounting type | Side-mounting |
|---|---|
| Cooling capacity(W) | 1150/1300 |
| Setting Temperature Range(℃) | 25~45 |
| Use Area Temperature(℃) | 20~50 |
| Use Area Humidity(%RH) | 10~85 (No condensation) |
| External dimensions(mm) | H900×W400×D250 |
| Weight(kg) | 36 |
| Coating Color | Munsell 5Y 7/1 Equivalent color of light beige |
| Rated Voltage(V) | Single-phase AC100 |
| Consumption Current: Rated(A) | 7.5/7.2 |
| Consumption Current: MAX(A) | 8.6/9.0 |
| Starting Current(A) | 22.3/20.5 |
| Consumption wattage: Rated(W) | 620/690 |
| Consumption wattage: MAX(W) | 770/870 |
| Noise Resistance | LEVEL4 by Fast Transient / Burst Immunity Test |
| Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
| Dust prevention / dust proof protection class | Equivalent to IP54 (internal circulation route) |
| Refrigerant / Fill ration(g) | R407C 330g |
| Noise (dB (A)) | Approx. 68/72 |
| External Output | Alarm output (No-voltage/normal open: resistive load 250V 2A) |
| Display | Internal temperature/Error display LED/RUN LED |
Note)
Cooling capacity : Rated capacity value when external temperature is 35°C, internal setting temperature is 35°C. (measurement conditions:JIS-C-9612 air enthalpy method))
Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.
Rating Value : 35°C ambient temperature, ambient humidity RH 40%.
MAX value: use area temperature at the maximum use area temperature allowed, use area humidity of 40%RH.
Allowable ambient temperature: When used continuously at a low ambient temperature (15 to 20 °C or less), be sure to turn off the power supply as there is a possibility the compressor may operate at a high load.
Non-draining function operating range: At an ambient temperature/panel internal temperature of 35 °C or less and an ambient humidity/panel internal humidity of 85% or less.
Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
Reading an instruction manual well certainly before use and please use it right.
Accessories list
| Mounting bolt for main unit | 6 (M8×L25) |
|---|---|
| Drain hose | 1 (2m) |
| Insulation lock ties | 1 |
| Washer | 2(M6) |
| Spacer | 6 |
| Air direcrion louver | 1 |
| Mounting bolt for louver | 2 |
| Mounting nut | 6 (M8) |
| Compound screw | 2 (M8) |
| Packing | (Long) 2 / (Short) 2 |
| Instruction manual | 1 |
Replacement parts list
| Condenser side Fan | Circulating fan for G1310LE |
|---|---|
| Evaporator side Fan | Outside air fan for G1310LE |
| Filter | ENC-F-49(2 pieces) |
| Evaporization filter | Vaporization filter for G1310LE |
| Control PCB | Substrate for G1310LE |
Note: Check with our sales representative as the delivery lead time varies depending on the inventory status.
*Note that the model, specifications and other details described are subject to change without notice.
External dimensions

(1) Power line : Cord length 3m
(2) Alarm Output Line : Cord length 3m
Diagram of Panel Cutout

*Figure seen from control board outside.
*Please keep screw pace on the occasion of processing.
*Standard panel cut will not be changed even if a model change is carried out (some exceptions apply), but the minimum panel cut dimensions are subject to change without notice.