Specifications
(50/60Hz)
Mounting type | Top-mounting |
---|---|
Cooling capacity(W) | 1400 |
Setting Temperature Range(℃) | 25~45 |
Use Area Temperature(℃) | 20~55 |
Use Area Humidity(%RH) | 10~85 (No condensation) |
External dimensions(mm) | H448×W590×D350 |
Weight(kg) | Approx. 31 |
Coating Color | Equivalent color of light beige 5Y 7/1 |
Rated Voltage(V) | Single-phase AC200~240 |
Consumption Current: Rated(A) | 4.5 |
Consumption wattage: Rated(W) | 750 |
Recommended breaker capacity (A) | 10 |
Vibration Resistance | JIS Z0200 Level1 |
Dust prevention / dust proof protection class | Equivalent to IP54 (internal circulation route) |
Refrigerant / Fill ration(g) | R1234yf 600g |
Noise (dB (A)) | Approx. 73 |
External Output | Rated voltage normally open : 250 VAC 2A/30 VDC 2A |
Display | Internal temperature/Error/RUN |
Cooling Capacity : Rated capacity value when ambient temperat ure is 35°C and ambient humidity is 40%RH, power voltage : 200V. (Test method :JIS B 8615-1 the inside of a air enthalpy test method)
Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.
Dust prevention / dust proof protection class : Excluding drain port section.
Reading an instruction manual well certainly before use and please use it right.
External dimensions
Warning output and external communication cables are optional.
Warning output cable:OP-ENCPR-OTR003
External communication cable:OP-ENCPR-OTR004