The precision chiller PCU-R Series has a cooling cycle utilizing three electronic expansion valves and an innovative parallel task control that provides PID control of the chiller’s parallel heaters. This feature combines wide range with precision control, something that older inverter control and hot gas control chillers had trouble achieving. With a minus 10 to 80℃ temperature range and ±0.5℃ accuracy, these chillers can be used in a wide range of situations that require precise cycling water temperature regulation. Moreover, a multistage centrifugal pump using special blades that rapidly rotate in a horizontal direction achieves excellent water feeding capacity and pulsation-free, high-pressure pumping.

Specifications

(50 / 60Hz)

Cooling scheme Water-cooling type
Cooling capacity (W) 3100 / 3400
Heating capacity / rapid heating(W) 2000
Heating capacity / controlled heating(W) 1000
Circulated water Pure water or distilled water (1μs/cm or more), ethylene glycol solution (concentration: 30% max.)
Temperature stability (℃) ±0.05 (High precision mode)
Use Area Temperature (℃) 5~40
Water setting temperature range (℃) -10 to 80
Circulating pump/Rated output (W) 600
Circulating pump/Flow rate (ℓ/min) 18/20
Circulating pump/Head (m) 30/43
Maximum tank capacity (ℓ) 30
Cooling water / Temperature range (℃) 5~40
Cooling water / Pressure (Mpa) 0.1~0.5
Cooling water / Flow rate (ℓ/min) 17
Dimensions (mm) H1000×W440×D800
Weight (kg) 105
Rated Voltage (V) 3-phase AC200
Power Consumption/MIN (A) 1460/1810
Power Consumption/MAX (W) 4460/4810
Current Consumption/MIN (A) 4.9/5.9
Current Consumption /MAX (A) 14.9/15.9
Voltage source capacity (kVA) 7
Refrigerator R407C 650g
Noise (dB) 53/53
Safety circuit / Compressor Temperature protector (135℃ OFF), overcurrent relay
Safety circuit / Refrigeration cycle Pressure switch
Safety circuit / Circulating water circuit Water pressure sensor, float switches for water shortage/water supply/water full detection
Safety circuit/Pump Overcurrent relay
Safety circuit / Fan motor Overcurrent relay
Safety circuit / Heater Overheat prevention thermostat (90℃ OFF), electric current fuse Alarm output
Input/Output / Alarm output a-contact, no voltage (250 VAC/2 A/resistive load)
Input/Output / Water temperature upper/lower limit output a-contact, no voltage (250 VAC/2 A/resistive load)
Input/Output / Water supply valve/operation output a-contact, no voltage (250 VAC/2 A/resistive load)
Input/Output / External control input No-voltage input
Input/Output / Emergency stop input No-voltage input
Input/Output / RS-232C Half-duplex, 3-wire, 1-to-1
Input/Output / External temperature sensor input Pt100
Safety measures Compressor conditioning timer, closing assist pump, fixing adjuster, double safety pan structure
Functions Circulating water pressure display, heater power display, pump operating time display, freeze-proof operation, digital filter, password setting, automatic tuning, ON/OFF timer, key-lock, error history memory

Cooling capacity: Cooling capacity at a circulating water temperature of 20 °C, ambient temperature of 30 °C, and the circulating water rated flow rate.
Temperature stability: Accuracy at the main body temperature control reading at constant load, circulating water temperature of 20 °C, ambient temperature of 30 °C, and the circulating water rated flow rate. Specifications may not be fulfilled depending on the operating conditions.
Circulating water: Do not use pure water or ultrapure water (conductivity: 1 μS/cm or less, specific resistance: 10 MΩ/cm or more).
External dimensions: Excluding protrusions.
Rated flow rate: Flow rate of circulating water required to satisfy the cooling capacity and temperature accuracy.
Circulation pump: Value minus the pressure loss inside the main unit.
・For the actual installation, check the specifications and precautions stated in the instruction manual.
・Contact our nearest sales office if you need an instruction manual in advance for design purposes.

External dimensions

PCU-W3610R External dimensions

[List of pipe calibers]

(1) Circulating water outlet [caliber] Rc3/4
(2) Circulating water inlet [caliber] Rc3/4
(3) Primary safety pan outlet [caliber] Rc1/2
(4) Secondary safety pan outlet [caliber] Rc1/4
(5) Heater tank outlet [caliber] Rc1/2
(6) Tank outlet [diameter] Rc1/2
(7) Overflow outlet [caliber] Rc1/2
(8) Circulating water suction inlet [caliber] Rc1
(9) Cooling water inlet [caliber] Rc3/4