PAP mini Air-Cooled Precision Air ProcessorDespite its compact design, delivers temperature and humidity controlled air for clean spaces while cutting energy consumption by as much as 80%!
PAP01B / PAP01B-KJ
PAP03C / PAP03C-KJ
- Air Processing Capacity
- 0.7 to 4.0 m3/min
- Humidity Control Precision
- ±0.1℃
- Temperature Setting Range
- 18 to 30℃
- Humidity Control Precision
- ±1% ※KJ models only
- Possible Humidity Setting Range
- 45 to 75% ※KJ models only
Special Order Product
Noise Reducing Intake Duct / Circulation Intake Chamber
Ventilation Air Chamber / Compact Chamber Box
Table of Special Order Items Here
- Please contact ORION regarding custom built models with specifications outside the ranges listed herein.
Specifications
PAP01B (Temperature Control Type) |
PAP01B-KJ (Temperature and Humidity Control Type) |
|||
---|---|---|---|---|
Performance | Possible Temperature and Humidity Setting Ranges ※1 | ℃,% | 18 to 30 | 18 to 30,45 to 75 |
Temperature and Humidity Control Precision ※2 | ℃,% | ±0.1 | ±0.1,±1.0 | |
Cooling + Heating Output (50/60 Hz) ※3 | kW | 0.33/0.39 | 0.77/0.84 | |
(Maximum cooling capacity) | (kW) | (0.22/0.26) | (0.37/0.44) | |
Rated Processing Air Flow | m3/min | 0.7 to 1.0 | ||
Maximum External Static Pressure ※4 | Pa | 120/130 | 120/160 | |
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) ※1 | ℃,% | 15 to 35,30 to 70 | |
Temperature Gradient at Intake | ℃/h | Within ±1 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
External Dimensions (HxDxW) ※5 | mm | 346×500×412 | 765×620×390 | |
Product Mass | kg | (32) | (69) | |
Controlled Air Outlet Port | mm | Φ75 | Φ100 | |
Humidification Water | Water Quality | – | Deionized water (electrical conductivity:1-10 µS/cm) |
|
Maximum Moisuture Output ※6 | kg/h | – | 0.8 | |
Supply Temperature Range | ℃ | – | 10 to 40 | |
Connection Port Size | – | Rc1/4 | ||
Electrical Specifications | Power Supply ※7 ※10 | V(Hz) | Single-phase 100±10% (50/60) | |
Power Consumption | kW | 0.32/0.34 | 1.2/1.2 | |
Electric Current ※8 | A | 4.0/3.9 | 13/13 | |
Power Supply Capacity ※9 | kVA | 0.34/0.38 | 1.5/1.5 | |
Noise Level (50/60 Hz) ※10 | dB | 54/56 | 58/60 | |
Refrigerant | R134a | R407C | ||
Compressor Output | kW | 0.25 | 0.3 |
- The temperature and humidity control ranges noted do not necessarily indicate the actual possible controllable ranges. The actual controllable temperature and humidity ranges will depend on the temperature and humidity of the intake air as well as process air flow rate. Set the processing air flow according to the operating environment.
- When the intake air temperature and humidity are stable. Noted precision value displayed on the controller is for one point at the outlet port. When operating at the maximum rated air flow.
- When the intake (surrounding) air temperature and humidity are 30 ℃, 70 %, at a processing air flow of 1 m3/min .
- The eternal static pressure at the controlled air outlet side of the blower fan outlet side when operating at the maximum rated processing air flow.
- Height includes the outlet port.
- The figure noted is when operating at the top of the specified level of humidification.
- Plug the product into a dedicated outlet in order to prevent voltage drops.
- Maximum value within the range of the product’s specifications.
- When operating at the maximum operating current within the specified range.
- Includes a 2 m power cord.
- Ducting should be insulated, and ducting length should be kept as short as possible. (Recommended maximum length: 3 m)
Scroll
PAP03C (Temperature Control Type) |
PAP03C-KJ (Temperature and Humidity Control Type) |
|||
---|---|---|---|---|
Performance | Possible Temperature and Humidity Setting Ranges ※1 | ℃,% | 18 to 30 | 18 to 30,45 to 75 |
Temperature and Humidity Control Precision ※2 | ℃,% | ±0.1 | ±0.1,±1.0 | |
Cooling + Heating Output (50/60 Hz) ※3 | kW | 1.65/1.85 | 1.8/2.12 | |
(Maximum cooling capacity) | (kW) | (1.15/1.35) | (1.2/1.42) | |
Rated Processing Air Flow※1 | m3/min | 2.0 to 4.0 | ||
Maximum External Static Pressure ※4 | Pa | 110/150 | 110/150 | |
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) ※1 ※5 | ℃,% | 15 to 40,30 to 70 | |
Temperature Gradient at Intake | ℃/h | Within ±1 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
External Dimensions (HxDxW) ※6 | mm | 1070×590×480 | 1350×680×520 | |
Product Mass | kg | (95) | (135) | |
Controlled Air Outlet Port | mm | Φ98 | ||
Humidification Water | Water Quality | – | Deionized water (electrical conductivity:1-10 µS/cm) |
|
Maximum Humidification Output ※7 | kg/h | – | 2.3 | |
Supply Temperature Range | ℃ | – | 10 to 40 | |
Connection Port Size | – | Rc1/4 | ||
Electrical Specifications | Power Supply ※8 | V(Hz) | Three-phase 200 ±10% (50/60) | |
Power Consumption※9 | kW | 0.75/0.85 | 2.7/3.1 | |
Electric Current ※10 | A | 3.8/3.8 | 11/12 | |
Power Supply Capacity ※11 | kVA | 1.4 | 4.0 | |
Noise Level (50/60 Hz) | dB | 64/65 | 65/66 | |
Refrigerant | R410A | |||
Compressor Output | kW | 0.8 | 0.85 |
- The temperature and humidity control ranges noted do not necessarily indicate the actual possible controllable ranges. The actual controllable temperature and humidity ranges will depend on the temperature and humidity of the intake air as well as the process air flow rate. Set the processing air flow according to the operating environment.
- When the intake air temperature and humidity are stable. Noted precision value displayed on the controller is for one point at the outlet port. When operating at the rated processing air flow (3m³/min). After operation starts, for approx. 2 minutes the temperature will temporarily fluctuate due to operation while the compressor oil returns. Also, if the target humidity is high, and depending on the timing of the supply of the humidification water, the precision previously noted may not be able to be maintained. In such cases, by adjusting parameters related to supply water, the amount of fluctuation can be reduced.
- When the intake (surrounding) air temperature and humidity are 30 ℃, 70 %, at a processing air flow of 3 m³/min .
- When the processing air flow is 3 m³/min.
- See the operating manual for details regarding the possible operating range of ambient temperature and humidity.
- Height includes the outlet port.
- The figure noted is when operating at the top of the specified level of humidification.
- The source voltage phase unbalance should be less than ±3 %.
- The intake (surrounding) air temperature and humidity are 30 ℃, 70 %, at a processing air flow of 3 m3/min .
- Maximum value within the range of unit specifications.
- The figure noted is when the product is operating at the highest capacity of its normal operating range.
- Ducting should be insulated, and ducting length should be kept as short as possible. (Recommended maximum length: 3 m)