The high-performance chiller PCU-SL Series’ innovative IOF sensor constantly monitors circulation water inlet and outlet temperature and circulation water flow rate. By making it possible for the chiller to detect changes in load and flow faster and more accurately caused by production processes than any other chiller, the sensor quickly stabilizes circulation water temperature. What’s more, PCU-SL Series chillers have an innovative structure that gives them the toughness needed for harsh environments. Additionally, a structure that separates the top and bottom of the unit provides IPX4 water protection that withstands tests even more demanding than JIS standards, thus making it possible to install the chiller outdoors with confidence.
Specifications
(50 / 60Hz)
Cooling scheme | Water-cooling type |
---|---|
Cooling capacity (W) | 14200 |
Heating capacity (W) | 2500 |
Circulated water | Pure water (over 1μs/cm), distilled water, ethylene glycol (less than 30% density), top water |
Temperature stability (℃) | ±0.1 |
Use Area Temperature (℃) | 2~45 |
Water setting temperature range (℃) | -5 to 45 |
Circulated water temperature range (Clear water) (℃) | 5~45 |
Circulated water temperature range (Anti-freeze water) (℃) | -5~45 |
Circulated water flow rate range (L/min) | 20~70 |
Circulated water pressure range (Mpa) | 0.7 or less |
Circulating pump/Head (m) | 51m (45L/min / 3600rpm) (max. lift 71m) |
Maximum tank capacity (ℓ) | 35 |
Cooling water / Temperature range (℃) | 5~45 |
Dimensions (mm) | H1349×W850×D750 |
Coating Color | DIC G-260 (Munsell : N7.5 or suitable color) |
Weight (kg) | 139 |
Rated Voltage (V) | 3-phase AC200~230V |
Power Consumption (kW) | 4.6 |
Current Consumption/MIN (A) | 14.0 |
Current Consumption /MAX (A) | 19.0 |
Voltage source capacity (kVA) | 7.6 |
Recommended breaker capacity (A) | 30 |
Components / Compressor | Shutting tightly Roundabout system |
Components / Condenser | Plate-type heat exchanger |
Components / Refrigerator | Plate-type heat exchanger |
Components / Evaporator | 70 |
Components / Circulating pump | Multistep spiral dipping mandrel |
Refrigerator | R410A 1250g |
Noise (dB) | 58 |
Safety circuit / Compressor | Motor protector |
Safety circuit / Refrigeration cycle | Pressure switch |
Safety circuit / Circulating water circuit | Water pressure sensor, float switches for water shortage |
Input/Output / Alarm output | No-voltage/normal open (250 VAC/2 A) |
Input/Output / Water temperature upper/lower limit output | No-voltage/normal open (250 VAC/2 A) |
Input/Output / Water supply valve/operation output | No-voltage/normal open (250 VAC/2 A) |
Input/Output / Operation stop output | No-voltage/normal open (250 VAC/2 A) |
Input/Output / Pump output | No-voltage/normal open (250 VAC/2 A) |
Input/Output / Emergency stop input | No-voltage input |
Input/Output / Operation stop input | No-voltage input |
Input/Output / Error reset input | No-voltage input |
Input/Output / Ethernet | Communication standard: Ethernet 10BASE-T / 100BASE-TX Communication protocol: Socket (TCP / IP), MC protocol (UDP / IP) IP address: IPv4 |
Safety measures | CE (Low-voltage command, EMC command), UL (ETL Certification) |
Others | Waterproofing: IPx4 or equivalent Vibration resistance: MIL-STD-810F or equivalent Safety standards: CE (Low Voltage Directive, EMC Directive), UL (ETL Certification) Operating noise level (dB): 69 |
*Cooling capacity, power consumption, current consumption rating: 20 ºC circulating water temperature, 45L/min circulation water flow rate, 32ºC ambient temperature and cooling water rated flow rate (cooling water volume requires rated performance).
*Heating capacity: During start-up operation at an ambient temperature of 40 °C. Varies depending on the ambient temperature.
*Circulated water: Use water with a purity of 1 μS/cm or more (low purity). Pure water: Water quality standards of The Japan Refrigeration and Air Conditioning Industry Association (JRA GL-02-1944)
* Required cooling water flow rate: The amount of cooling water required for the rated capacity.
* Temperature stability: Depends on the display value of the main body temperature indicator at a constant load.
*MAX current consumption: When the circulating water temperature is 20 °C, the circulating water flow rate is 70 L/min, and circulating water temperature is 45 °C.
*Vibration resistance: Up to 100 Hz under the test conditions of the MIL-STD-810F standard.
*Operating noise: Measured at a horizontal distance of 1 m and height of 1 m.