A tear drop shape jaw with the conductor size 55 mm: Convenient to use at a small-sized office and factory

・Current up to 1000A rms
・Voltage up to 1000V rms
・Harmonics up to 30th
・Various measurement functions: current, voltage, power, harmonics
   and phase detection
・LCD can display simultaneously the values of voltage and frequency
   or power and power factor
・Each degree of harmonics can be shown on the LCD of the tester

CE    TRUE RMS    φ55    Backlight

1.Various measurement functions

〇 Measurements of current, voltage, power, harmonics and phase detection are possible.
〇 True RMS: Indicates a correct value at the distorted waveform.
〇 Functions of PEAK, MAX, MIN, AVG are available. Easy to check the temporal change in the power source.
〇 LCD can display simultaneously the values of voltage and frequency or power and power factor.

2.Power measurement

Power measurement on any wiring system is possible.

KEW 2060BT can perform Single-phase 2-Wire / Single-phase 3-Wire and balance and unbalance measurements of Three-phase 3-Wire / Three-phase 4 Wire. The double display can simultaneously show many parameters like W & PF, W & deg, W & VA, W & Var, V & A, etc.

Various parameters such as active/reactive/apparent power,
power factor, phase differences (1P2W only) which are required for the power measurement can be measured.

Total 3-phase power can be measured in simple steps.

By setting the CT and VT ratio and measuring the secondary side of the transformation, the primary side value can be obtained.

3.Harmonics measurement

Harmonics of the voltage and current, which cause various failures at the field, can be measured. It is possible to measure and show each voltage and current harmonics up to 30th.
Total harmonics distortion factor is in two types of THD-R and THD-F. Each degree of harmonics can be shown on the LCD of the tester. Both the current value (or voltage value) and the content ratio can be displayed on the same screen.

4.Phase detection

 
Wiring connections 1P2W, 1P3W, 3P3W, 3P4W
Measurements and 
parameters
Voltage, Current, Frequency, Active power, Reactive power, 
Apparent power, Power factor(cosθ), Phase angle, 
Harmonics(THD-R/THD-F), Phase rotation
ACV
 
Range 1000V
Accuracy ±0.7%rdg±3dgt (40.0 – 70.0Hz)
±3.0%rdg±5dgt (70.1 – 1kHz)
Crest factor 1.7 or less
ACA
 
Range 40.00/400.0/1000A (3 range auto)
Accuracy ±1.0%rdg±3dgt (40.0 – 70.0Hz)
±2.0%rdg±5dgt (70.1 – 1kHz)
Crest factor 3 or less on 40.00A/400.0A range, 
3 or less 1500A peak on 1000A range
Frequency
 
Display Range 40.0 – 999.9Hz
Accuracy ±0.3%rdg±3dgt
Active power
 
Range 40.00/400.0/1000kW
Accuracy ±1.7%rdg±5dgt (PF1, sine wave, 45 – 65Hz) 
Apparent power
 
Range 40.00/400.0/1000kVA
Accuracy ±1dgt against each calculated value 
Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt
Reactive power
 
Range 40.00/400.0/1000kVar
Accuracy ±1dgt against each calculated value 
Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt
Power factor
 
Display Range -1.000 – 0.000 – +1.000
Accuracy ±1dgt against each calculated value 
Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt
Phase angle (1P2W only)
 
Display Range -180.0 – 0.0 – +179.9
Accuracy ±3.0°
Harmonics RMS(Content rate)
 
Analysis order 1st – 30th order
Accuracy ±5.0%rdg ± 10dgt (1 – 10th)
±10%rdg ± 10dgt (11 – 20th)
±20%rdg ± 10dgt (21 – 30th)
Total harmonics THD-R/THD-F 
 
Display Range 0.0% – 100.0%
Accuracy ±1dgt against the calculated results of each measured value
Phase rotation ACV 80 – 1100V (45 – 65Hz)
Other functions MAX/MIN/AVG/PEAK, Data hold, Back light, Auto power off
General
 
Power source LR6(AAA)(1.5V) ×2
Continuous 
measuring time
Approx. 58 hours
Conductor size φ55mm max.
Dimensions / Weight 247(L) × 105(W) × 49(D) mm / Approx.490g(including batteries)
Applicable Standards IEC 61010-1, IEC 61010-2-032, IEC 61326-1,-2-2 (EMC), IEC 60529 (IP40)
CAT IV 300V / CAT lll 600V / CAT ll 1000V Pollution degree 2

Accessories 7290 (Voltage test lead set)
9198 (Carrying case)
LR6(AAA)×2, Instruction Manual