PAP03A-D(-CE) / PAP06A-D(-CE) /
PAP10A-D
- Air Processing Capacity
- 3 to 12 m3/min
- Temperature Setting Range
- 18 to 30℃
- Humidity Setting Range
- 20 to 40%
※Does not support humidification.
- Temperature and Humidity Control Precision
- ±0.2℃ / ±2%
- Instant dehumidification and precision air processing.
Special Order Product
Noise Reducing Intake Duct / Circulation Intake Chamber
Exhaust Chamber
Table of Special Order Items Here
- Please contact ORION regarding custom built models with specifications outside the ranges listed herein.
Features
Can instantly cool 30℃, 55% fresh air down to 23℃, 28%!
Achieves defrost-free performance relying on the refrigeration cycle only, with an indusrty top-class dew point of 3.5℃.
The PAP-D Series: Precision Air Processing AND Dehumidification Combined
Of Course Heater-less! And Compressor Speed Control for Energy Savings as much as 65%!
Once the set humidity is attained, compressor speed conrrol takes over for energy savings.
CE Certified Model Lineup
UL/CSA61010-1 Conformity Evaluation Completed / Conformity Report Available for Submission
※PAP03A-D-CE, PAP06A-D-CE
Applications
- Pharmaceutical and Supplement Filling Processes
- Rust and Condensation Prevention for Precision Electronic Parts
- One-Pass Dry Booth Powder Mixing, etc.
- Analysis and Measurement in Low Humidity Environments
- Low Humidity Storage of Adsorption Materials and Samples
- Prevention of Moisture Adsorption in Highly Functional Films
Specifications
Air Cooled | ||||
---|---|---|---|---|
PAP03A-D | PAP03A-D-CE | |||
Performance | Possible Temperature and Humidity Setting Ranges ※1 | ℃,% | 18 to 30, 20 to 40 | |
Temperature and Humidity Control Precision ※2 | ℃,% | ±0.2, ±2 (Does not support humidification.) |
||
Possible Controlled-Air Dew Point (Lower Limit) ※3 | ℃ | 3.5 | ||
Maximum Cooling Capacity ※4 | kW | (3.7) | ||
Heating Capacity ※5 | kW | (0.3) | ||
Rated Processing Air Flow | m3/min | 3 to 5 | ||
Maximum External Static Pressure ※6 | Pa | 500 (3m3/min) |
||
Pa | 100 (5m3/min) |
|||
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) | ℃, % | 17 to 35, 30 to 70 | |
Temperature Gradient at Intake | ℃/h | Within ±1 | ||
Humidity Gradient at Intake | %/h | Within ±5 以内 | ||
Cooling-Water Water-Temperature Gradient | ℃/h | – | ||
External Dimensions ※7 | mm | (1310×820×661) | (1654×820×661) | |
Product Mass | kg | (210) | (230) | |
Controlled Air Outlet Port | mm | Φ150 | ||
Electrical Specifications | Power Source ※8 | V(Hz) | Three-phase 200 ±10% (50/60) | |
Power Consumption ※9 | kW | 0.8 to 2.9 | ||
Electric Current ※10 | A | 11.3 | ||
Power Supply Capacity ※11 | kVA | 4.7 | ||
Operation Control Method | Heat Pump Balance Control (Super Reheat Spec. Models) | |||
Chiller Compressor Output | kW | 1.7 | ||
Refrigerant | R410A | |||
CE Marking | – | Built to Order |
Air Cooled | ||||
---|---|---|---|---|
PAP06A-D | PAP06A-D-CE | |||
Performance | Possible Temperature and Humidity Setting Ranges ※1 | ℃,% | 18 to 30, 20 to 40 | |
Temperature and Humidity Control Precision ※2 | ℃,% | ±0.2, ±2 (Does not support humidification.) | ||
Possible Controlled-Air Dew Point (Lower Limit) ※3 | ℃ | 3.5 | ||
Maximum Cooling Capacity ※4 | kW | (6.6) | ||
Heating Capacity ※5 | kW | (0.7) | ||
Rated Processing Air Flow | m3/min | 6 to 8 | ||
Maximum External Static Pressure ※6 | Pa | 500 (6m3/min) |
||
Pa | 300 (8m3/min) |
|||
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) | ℃, % | 17 to 35, 30 to 70 | |
Temperature Gradient at Intake | ℃/h | Within ±1 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
Cooling-Water Water-Temperature Gradient | ℃/h | – | ||
External Dimensions ※7 | mm | (1610×1150×770) | (1802×1150×770) | |
Product Mass | kg | (330) | (350) | |
Controlled Air Outlet Port | mm | Φ200 | ||
Electrical Specifications | Power Source ※8 | V(Hz) | Three-phase 200 ±10% (50/60) | |
Power Consumption ※9 | kW | 1.3 to 4.1 | 1.6 to 4.4 | |
Electric Current ※10 | A | 17.2 | 18.3 | |
Power Supply Capacity ※11 | kVA | 6.6 | ||
Operation Control Method | Heat Pump Balance Control (Super Reheat Spec. Models) | |||
Chiller Compressor Output | kW | 3.0 | ||
Refrigerant | R410A | |||
CE Marking | – | Built to Order |
Air Cooled | |||
---|---|---|---|
PAP10A-D | |||
Performance | Possible Temperature and Humidity Setting Ranges ※1 | ℃,% | 18 to 30, 20 to 40 |
Temperature and Humidity Control Precision ※2 | ℃,% | ±0.2, ±2 (Does not support humidification.) | |
Possible Controlled-Air Dew Point (Lower Limit) ※3 | ℃ | 3.5 | |
Maximum Cooling Capacity ※4 | kW | (10.5) | |
Heating Capacity ※5 | kW | (1.1) | |
Rated Processing Air Flow | m3/min | 10 to 12 | |
Maximum External Static Pressure ※6 | Pa | 500 (10m3/min) |
|
Pa | 200 (12m3/min) |
||
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) | ℃, % | 17 to 35, 30 to 70 |
Temperature Gradient at Intake | ℃/h | Within ±1 | |
Humidity Gradient at Intake | %/h | Within ±5 | |
Cooling-Water Water-Temperature Gradient | ℃/h | – | |
External Dimensions ※7 | mm | (1860×1200×990) | |
Product Mass | kg | (450) | |
Controlled Air Outlet Port | mm | Φ200 | |
Electrical Specifications | Power Source ※8 | V(Hz) | Three-phase 200 ±10% (50/60) |
Power Consumption ※9 | kW | 1.6 to 5.3 | |
Electric Current ※10 | A | 20.2 | |
Power Supply Capacity ※11 | kVA | 7.2 | |
Operation Control Method | Heat Pump Balance Control (Super Reheat Spec. Models) | ||
Chiller Compressor Output | kW | 3.0 | |
Refrigerant | R410A | ||
CE Marking | – |
- The temperature and humidity control ranges noted do not necessarily indicate the actual possible controllable ranges. The actual controllable temperature and humidity ranges will depend on the temperature and humidity of the intake air.(This product does not include a humidification function.)
- When the intake air temperature and humidity are stable. Controller display precision at a single discharge port location. Over-dehumidification may occur depending on operating conditions.
- The attainable dew point will depend on the condition of the intake air.
- Value is the stand-alone capacity of the built in evaporator.
- Value indicates the difference in capacity between the built-in heater and evaporator.
- The eternal static pressure at the controlled air outlet side when the blower fan is operating at 60 Hz, and the product is operating at the prescribed air flow.
- Height includes the discharge port.
- The maximum allowable source voltage phase imbalance is ±3%.
- Minimum and maximum values are when operating under the specified operating ranges.
- Maximum value is when operating under the specified operating ranges.
- The maximum current when operating under the specified operating ranges.