Permanent vibration monitoring for systems such as motor, pump and blower.
Monitoring system suitable for multi-channel measurement. Frequency range, measurement range or output signal can be customized.
Features
A wide range of compatible sensors
Selectable from electrodynamic velocity sensor or piezoelectric sensor.
Electrodynamic velocity sensors
Specialized in medium frequency (up to 1,000 Hz) vibration detection. Suitable to velocity monitoring.
Model | VP-3144C/D | VP-3354 A (Horizontal only) |
VP-3364 A (Vertical only) |
VP-3134AEX | VP-3213 AC/AD | VP-3133 HEX/VEX |
---|---|---|---|---|---|---|
Sensitivity | 10 mV/(mm/s) | 10 mV/(mm/s) | 10 mV/(mm/s) | 17.5 mV/(mm/s) | 17.5 mV/(mm/s) | |
Natural frequency | 14 Hz | 14 Hz | 14 Hz | 4.5 Hz | 4.5 Hz | |
Operating temperature range | -20 to +80℃ | -20 to +80℃ | -20 to +70℃ | -20 to +70℃ | -20 to +70℃ | |
Structure | Drip-proof (Equivalent to IP32) | Water-proof (Equivalent to IP66) | Flame-proof (EX d ⅡBT4Gb) | Drip-proof (Equivalent to IP32) | Flame-proof (EX d ⅡBT4Gb) | |
Outward appearance |
Type C |
Type AC |
||||
Notes | High sensitivity /medium frequency | Medium frequency /2-directional | Medium frequency /3-directional | Medium frequency | Low frequency /horizontal only | Low frequency / HEX (horizontal only), VEX (vertical only) |
Other sensors for high temperature or waterproof are also available. Please contact .
Piezoelectric sensors
Specialized in high frequency (over 1,000 Hz) vibration detection. Suitable to acceleration monitoring.
Model | VP-A52IW | HS-100I |
---|---|---|
Sensitivity | 5 mV/(m/s2) | 50 mV/G |
Natural frequency | 35 kHz | 24 kHz |
Operating temperature range | -30 to +110℃ | -20 to +80℃ |
Structure | Insulative and water proof | Safe and explosion proof (Ex iaⅡC T4 Ga) |
Outward appearance | ||
Notes | Insulated | Insulated |
Multi-channel
Maximum 12 channel per 1 system is available. Range and function can be set individually per every channel.
Application Example
Cables are laid out between sensors located on a large sized motor of home power generator and a monitoring system housed in a control panel. Monitoring systems can monitor vibration values and output the alarm in an emergency.
Outline Drawing
Unit: mm
A | B | C | D | E | F | G | H | I | ||
---|---|---|---|---|---|---|---|---|---|---|
Channel | Type 1 channel | 90 | 170 | 300 | 88 | 132 | 90 | 148 | 162 | 50 |
Type 3 channel | 210 | 149 | 300 | 160 | 132 | 180 | 143 | 100 | 195 | |
Type 6 channel | 300 | 149 | 300 | 250 | 132 | 270 | 143 | 100 | 285 | |
Type 9 channel | 390 | 149 | 300 | 340 | 132 | 360 | 143 | 100 | 375 | |
Type 12 channel | 480 | 149 | 300 | 430 | 132 | 450 | 143 | 100 | 465 |