Hard Case Model
• In addition to the facility for precision measurement, test leads for simplified two wire measuring system also supplied as standard accessories. (unit can be hung from the neck for simplified measurement)
• The latest circuit design permits the instrument to operate with the minimum of influence from earth voltage and earth resistance of auxiliary earth spikes.
• Dust and drip proof. (designed to IEC 60529 IP54)
• Earth resistance value can be read directly from the scale.
• Designed to meet IEC 61010-1 safety standard.
• Capable of measuring earth voltage.
• Small and lightweight. Shock resistant new case material.
• 2mA measuring current permits earth resistance tests without tripping earth leakage current breakers in the circuit under test.
• Lead wire connection to C and P terminals and proper auxiliary earth resistance can be checked by “OK” lamp. Lead wire connection to C and E terminals is good when “OK” lamp is illuminated
Hard case
Useful options for measurement
Adapter to enable use of ather test leads. (MODEL 8259)
Earth resistance measurement |
x1Ω | x10Ω | x100Ω | |
---|---|---|---|---|
Measuring range | 0 – 12 Ω | 0 – 120 Ω | 0 – 1200 Ω | |
Accuracy | ±3% of full scale | |||
Earth voltage measurement | ||||
Measuring range | 0 – 30V AC (50/60Hz) | |||
Accuracy | ±3% of full scale | |||
Overload protection | Earth Resistance: 276V AC/DC (10 seconds) Earth Voltage: 276V AC/DC (10 seconds) |
|||
Applicable Standards | IEC 61010-1 CAT III 300V Pollution Degree 2, IEC 61010-2-030, IEC 61557-1, -5, IEC 60529 (IP54) |
|||
Power source | R6 (AA) (1.5V) × 6 | |||
Dimensions | 105(L) × 158(W) × 70(D)mm (including case lid) | |||
Weight | Approx. 600g (including batteries and case lid) | |||
Accessories | 7095A (Earth resistance test leads [red-20m, yellow-10m, green-5m/1set]) 7127B (Simplified measurement probe) 8032 (Auxiliary earth spikes [2spikes/1set]) 9121 (Shoulder strap) 9164 (Carrying case [Hard]) R6 (AA) × 6, Instruction Manual |
|||
Optional | 7245A (Precision measurement cord set) 8259 (Adapter for measurement terminal) 9084 (Soft case) |